Your client has installed scalar devices to measure the solar energy generated (Export) and the energy received (Import) from the National Grid. This data is stored in separate measuring components (registers).
The validation rules are generally the same for both measuring components, but there is one exception. The Negative Consumption check applies only to energy received (import).
Which two are possible configurations resulting in the Negative Consumption rule being checked for energy received (import) only? (Choose two.)
Demetra
6 days agoRossana
17 days agoPeggy
18 days agoJanella
24 days ago