Deal of The Day! Hurry Up, Grab the Special Discount - Save 25% - Ends In 00:00:00 Coupon code: SAVE25
Welcome to Pass4Success

- Free Preparation Discussions

Oracle Exam 1Z0-996-22 Topic 1 Question 36 Discussion

Actual exam question for Oracle's 1Z0-996-22 exam
Question #: 36
Topic #: 1
[All 1Z0-996-22 Questions]

Your client has installed scalar devices to measure the solar energy generated (Export) and the energy received (Import) from the National Grid. This data is stored in separate measuring components (registers).

The validation rules are generally the same for both measuring components, but there is one exception. The Negative Consumption check applies only to energy received (import).

Which two are possible configurations resulting in the Negative Consumption rule being checked for energy received (import) only? (Choose two.)

Show Suggested Answer Hide Answer
Suggested Answer: A

Contribute your Thoughts:

Demetra
6 days ago
Option C makes the most sense to me. Creating two separate VEE groups seems like the best way to apply the Negative Consumption rule only to the energy received (import) data.
upvoted 0 times
...
Rossana
17 days ago
I'm not sure about creating two different VEE groups. Maybe we can use the Skip Flag in the VEE rule instead.
upvoted 0 times
...
Peggy
18 days ago
I agree with Janella. We can also create two different VEE groups to check the rule only for energy received.
upvoted 0 times
...
Janella
24 days ago
I think we should modify the base VEE rule for the Negative Consumption check.
upvoted 0 times
...

Save Cancel
az-700  pass4success  az-104  200-301  200-201  cissp  350-401  350-201  350-501  350-601  350-801  350-901  az-720  az-305  pl-300  

Warning: Cannot modify header information - headers already sent by (output started at /pass.php:70) in /pass.php on line 77