Your client has installed scalar devices to measure the solar energy generated (Export) and the energy received (Import) from the National Grid. This data is stored in separate measuring components (registers).
The validation rules are generally the same for both measuring components, but there is one exception. The Negative Consumption check applies only to energy received (import).
Which two are possible configurations resulting in the Negative Consumption rule being checked for energy received (import) only? (Choose two.)
Fausto
29 days agoHelene
5 days agoElbert
12 days agoFarrah
15 days agoElbert
18 days agoBrock
1 months agoLeeann
1 months agoLili
1 months agoTeri
2 days agoGail
16 days agoJosphine
1 months agoJonelle
8 days agoDelsie
9 days agoVan
11 days agoDemetra
2 months agoChanel
20 days agoElvera
26 days agoAlana
1 months agoCristina
1 months agoRossana
2 months agoPeggy
2 months agoJanella
3 months ago