Which of the following conditions must be considered when determining the spacing and location of smoke detectors?

I . Ceiling height

II . Detector sensitivity

III . Ambient environment

IV . Ventilation or airflow

Show Suggested Answer Hide Answer
Suggested Answer: D

The proper spacing and placement of smoke detectors are critical to their effectiveness. These factors are addressed in NFPA 72, National Fire Alarm and Signaling Code.

Ceiling height (I): Ceiling height affects smoke behavior. Higher ceilings allow smoke to cool and stratify, delaying detection. Adjustments must be made for ceilings greater than 10 feet.

Detector sensitivity (II): Smoke detector sensitivity determines how quickly it responds to smoke. Placement must account for conditions that may impact its performance.

Ambient environment (III): Environmental conditions such as temperature, humidity, and dust can affect smoke detector operation. Locations like kitchens or dusty areas may require specialized detectors.

Ventilation or airflow (IV): Airflow patterns created by HVAC systems, vents, or fans can direct smoke away from detectors, delaying activation. Proper placement ensures smoke reaches the detector efficiently.


NFPA 72, Chapter 17: Detector spacing, location, and environmental considerations.

Contribute your Thoughts:

Vincenza
3 days ago
Hmm, I bet the exam writer is an HVAC engineer. C is the way to go, folks.
upvoted 0 times
...
Dottie
4 days ago
Ah, the joys of fire code compliance. I'll go with C - no need to overthink it.
upvoted 0 times
...
Susana
13 days ago
Haha, someone's been reading their fire safety manual! I'd go with D, just to be thorough.
upvoted 0 times
Julianna
16 hours ago
I agree, D seems like the safest option.
upvoted 0 times
...
...
Leonardo
17 days ago
I believe the correct answer is D) I, II, III, and IV because all conditions play a role in determining the spacing and location of smoke detectors.
upvoted 0 times
...
Ty
23 days ago
I agree, C is the right answer. The ambient environment and ventilation patterns can significantly impact detector performance.
upvoted 0 times
Junita
4 days ago
I disagree, I believe the correct answer is A. Ceiling height and ventilation are the key factors to consider.
upvoted 0 times
...
Barney
14 days ago
I think the answer is D. All of those conditions are important for determining the spacing and location of smoke detectors.
upvoted 0 times
...
...
Cherrie
1 months ago
I agree. Ceiling height, detector sensitivity, ambient environment, and ventilation are all important factors.
upvoted 0 times
...
Lorriane
1 months ago
I think we should consider all the conditions mentioned in the question.
upvoted 0 times
...
Rosalia
2 months ago
Definitely I, III, and IV. Ceiling height and airflow are crucial factors for proper smoke detector placement.
upvoted 0 times
Tyisha
14 days ago
So, the correct conditions to consider are I, III, and IV then.
upvoted 0 times
...
Annice
24 days ago
I agree, those factors can greatly affect the effectiveness of the detectors.
upvoted 0 times
...
Tawna
25 days ago
Yes, all four conditions - ceiling height, detector sensitivity, ambient environment, and ventilation - are important for determining the spacing and location of smoke detectors.
upvoted 0 times
...
Shenika
29 days ago
I think detector sensitivity and ambient environment should also be taken into consideration for optimal placement.
upvoted 0 times
...
Denise
1 months ago
I agree, ceiling height and airflow can greatly affect the effectiveness of smoke detectors.
upvoted 0 times
...
Renea
1 months ago
Ceiling height and airflow are definitely important for smoke detector placement.
upvoted 0 times
...
...

Save Cancel
az-700  pass4success  az-104  200-301  200-201  cissp  350-401  350-201  350-501  350-601  350-801  350-901  az-720  az-305  pl-300  

Warning: Cannot modify header information - headers already sent by (output started at /pass.php:70) in /pass.php on line 77